The HJ-DYZ-600 intelligent high-frequency switch-mode power system comprises a cabinet, AC distribution, rectifier modules (up to 12 fully configured), a monitoring module, and DC distribution. It offers comprehensive battery management-including low-voltage protection and optional load disconnect-plus temperature compensation, automatic voltage regulation, stepless current limiting, capacity calculation, online battery testing, and sleep energy-saving. Networked design with RS232/RS485 and dry-contact ports enables flexible networking, remote monitoring, and unattended operation, with full AC/DC surge protection and complete fault protection/alarm functions.
Send besked Få pris
| Miljøparametre | Driftsforhold | Transportforhold | Opbevaringsforhold | Gældende standarder | Bemærkninger | |||
| Kategori | Parameter | Enhed | ||||||
| Klimatiske forhold | Temperatur | Lav temperatur | ℃ | -33 | -40 | -40 | YD/T 1058-2000 Klausul 4.1.1 og 4.1.2 | Fuld belastningsstart ved −40 ℃; lineær 20% reduktion fra +55 til +65 ℃. |
| Høj temperatur | ℃ | 65 | 70 | 70 | ||||
| Temperaturændring | ℃/min | / | 1 | / | ETS 300 019-2-2 T2.3 | |||
| Betjening omgivelsestemperatur | ℃ | -33-65 | Ekstrem driftstemperatur ved fuld belastning | |||||
| Opbevaringstemperatur | ℃ | -40-70 | ||||||
| Fugtighed | Relativ fugtighed | % | 5-90 | 90 (40±2℃) | / | YD/T 1058-2000 Klausul 4.1.3 | Short-term test: 0-95%, max 95%, non-condensing | |
| Kondensation | Ja Nej | Ingen | Ingen | Ja | ||||
| Atmosfærisk tryk | Lavt tryk | kPa | 86 | 70 | 70 | YD/T 1058-2000 Klausul 4.1.4 | Kun modultestning | |
| Højt tryk | kPa | 106 | 106 | 106 | ||||
| Højde | m | ≤ 4000 | Over 2000 m, reduktion på 0.5 ℃ pr. yderligere 100 m | |||||
Bemærk: Specifikationerne kan ændres uden forudgående varsel med henblik på produktforbedring. Datablad
Fully digital interleaved PFC innovative control with limited bipolar ZVS full-bridge topology, current-doubler rectifier topology, and dual MCUs for fully digital monitoring
Rectifiers use PFC so AC input current matches the voltage waveform and phase; high system efficiency saves energy and reduces OPEX
High-frequency PWM conversion reduces switching losses and EMI, allowing installation inside switching equipment rooms
Intelligent battery management with continuously settable equalization/float voltages and charge current limits via controller or remote system; supports float, equalization, and battery testing
Equipotential design across the cabinet improves EMC and lightning protection
Den er velegnet til forskellige strømforbrugsscenarier, såsom beboelsesejendomme og erhvervskontorbygninger.
Vi er forpligtet til at yde hurtig, professionel support for at sikre, at dine energibehov altid bliver opfyldt med det højeste serviceniveau.
Vi er her for at besvare dine spørgsmål og levere de energiløsninger, der passer bedst til dine behov.